Processor |
Number |
8
to 32 12-Core 3.6GHz SPARC M6 processors
4 to 16 CMU boards (2 processors per CMU board) |
Architecture |
SPARC V9 architecture |
CPUs |
- Up to 96 compute threads per processor (3,072
max threads per system)
- 12 floating-point units per SPARC M6 processor
- 12 cryptography units per SPARC M6 processor
- On-chip Encryption Instruction Accelerators
with direct non-privileged support for
16 industry-standard cryptographic algorithms plus random number generation
in
each of the twelve cores: AES,
Camellia, CRC32c, DES, 3DES, DH, DSA, ECC,
Kasumi, MD5, RSA, SHA-1, SHA-224, SHA-256, SHA-384, SHA-512
|
Cache memory |
- Shared 48MB, 8 banked, Level 3 Cache
- 128KB Level 2 unified cache per core
|
Maximum Number of Domains |
- Up to 4 Dynamic domains
- Up to 512 Logical domains
|
Main
Memory
|
Capacities |
- 32 DIMM slots per processor (32 DIMM slots ×
32 processors = 1,024 slots max)
- 64 DIMM slots per CPU/Memory Board
- 32TB System maximum (1,024 slots × 32GB
DIMMS = 32TB)
- 16GB and 32GB 1066MHz DDR3 DIMMs supported
- All DIMMs on a CMU must be the same size and
type.
- DIMMs of different capacities can be used in
the same server with the limitation that all DIMMs in a CMU must have
the same capacity.
- Supported memory DIMM quantities on each CMU
board are 16 DIMMs (1/4 populated), 32 DIMMs (1/2 populated), and 64
DIMMs (fully populated). 48 DIMMs (3/4 populated) is not supported
|
Standard
Interfaces |
Ethernet |
Up to 32 10 GbE (100Mbps/1Gbps/10Gbps)
using configured Base I/O Cards |
PCI Express |
64 low-profile PCI Express 3.0 (x8 wired)
slots |
Network Management |
1 GbE port per System Processor |
Serial Management |
1 RJ-45 port per System Processor |
Internal
Mass Storage |
Disks |
Up to 32 600GB SAS disk drives or 300GB
SSDs |
Power
Supplies |
12 hot-swappable 7,000
Watt (AC) and redundant (6 + 6) power supplies
Three-phase Delta
For more information, see the SPARC
M6-32 Installation Guide. |
Environment
|
Power Supply Output Capacity |
7.0 KW |
AC power |
200 to 480 VAC
Three-phase center-point grounded (L1, L2, L3, Ground)
For more information, see the SPARC
M6-32 Installation Guide.
|
Nominal frequencies |
50-60 Hz input |
Output rating |
+12.2V @ 583A output |
Maximum AC RMS input current per power supply |
- 24A @ 200-240 VAC
- 12A @ 380-415 VAC
- 10A @ 480 VAC
|
Maximum AC RMS input current per power cord |
- 48A @ 200-240 VAC
- 24A @ 380-415 VAC
- 20A @ 480 VAC
|
Inrush Current |
- 88A peak (excluding EMI filter charging)
- Less than 48A RMS over one cycle
|
Protective earth current |
- Less than 2 mA per power cord (measured at 480
VAC)
- Less than 12 mA per server (measured at 480
VAC)
|
Heat output (cooling requirement) |
90,000 BTUs/hr (94,995 kJ/hr) - fully
configured server
For more information, see the SPARC
M6-32 Installation Guide. |
Use the online
power calculator to determine the power consumption for your specific
configuration. |
Power cords |
For more information, see the
SPARC
M6-32 Installation Guide. |
Temperature |
Operating:
Altitude up to 500 Meters (1640 ft): 5°
C to 35° C ( 41° F to 95° F)
Altitude up to 3000 Meters (9843 ft): 5° C to 29° C ( 41°
F to 84° F)
Nonoperating:
0° C to 50° C ( 32° F to 122° F), maximum altitude 12000
Meters (40000 ft) |
Humidity |
Operating:
20% to 80% relative humidity, noncondensing, 27° C (81° F) wet
bulb
Nonoperating: 93% relative humidity, noncondensing, 38° C (100.4°
F) wet bulb |
Altitude |
Operating:
Up to 3000M (9843 ft)
Nonoperating: Up to 12000 Meters (40000 ft) |
Regulations
Meets or exceeds the following requirements: |
Safety |
EN 60950-1: 2006+A11:2009, IEC 60950-1:2005+A1:2009 2nd Edition,
UL60950-1 2nd Edition,2011-12-19 ,CAN/CSA-C22.2 No.60950-1-01 2nd Edition
2011-12 |
EMC |
EN55022:2010 Class A, EN55024:2010, EN61000-3-2:2006+A1:2009+A2:2009,
EN61000-3-3:2008, ETSI EN300386:2012 (V1.6.1) , 47 CFR15 Subpart B (FCC)
Class A, ICES-003 Class A, AS/NZS CISPR22:2009+A1:2010, CISPR22:2008 Class
A |
Regulatory Markings |
CE, FCC, ICES-003, C-Tick, VCCI, EAC, BSMI, KC, cULus |
Other Marks |
European
Union directives: Restriction of Hazardous
Substances (RoHS) Directive 2011/65/EU |
Dimensions
and Weights |
Height |
2000 mm (78.7 in) |
Width |
With Side panels:
904 mm (35.6 in)
W/O Side panels: 876
mm (34.5 in) |
Depth |
With Doors:
1451 mm (57.1 in)
W/O Doors: 1362
mm (53.6 in)
Front door handle to rear door handle: 1482
mm (58.3 in) |
Weight (varies by configuration) |
1677 kg (3697 lbs) max |
Clearance
and Service Access |
Front |
914 mm (36 in) |
Rear |
914 mm (36 in) |
For more information, see the SPARC
M6-32 Installation Guide. |