Chassis |
- 1U, rackmount
- Power supplies: single or dual AC or DC, field replaceable
- Front: Power and HA status LEDs, physical system reset pinhole, console
- Rear: One NIU slot (signaling, media, and management interfaces)
- Optional mounting brackets for front, rear, or center mount in a 19 inch or 23 inch rack
|
Memory |
- 2GB for active configurations and logs
- 256MB internal flash memory for runtime image and backup configurations
- Optional storage expansion module for local Call Detail Record (CDR) backup
|
Content Addressable Memory (CAM) |
128K entries for static and dynamic Access Control lists (ACLs), media control rules,
and Address Resolution Protocol (ARP) entries
|
Network Interface Units (NIU) |
Basic Interface Unit |
- Four 10/100/1000 Mbps Ethernet copper ports (RJ-45 connector)
- Four 1000 Mbps Ethernet fibre or four 10/100/1000 Mbps copper ports (requires SFP transceivers)
- Four 10000 Mbps Ethernet fibre or four 10/100/1000 Mbps copper ports with inline IPsec/SRTP encryption
processors (requires SFP transceivers)
- Four 10000 Mbps Ethernet fibre or four 10/100/1000 Mbps copper ports with inline QoS measurement
processors (requires SFP transceivers)
- Four 10000 Mbps Ethernet fibre or four 10/100/1000 Mbps copper ports with inline IPsec/SRTP encryption
and QoS measurement processors (requires SFP transceivers)
|
Transcoding Interface Unit |
- Four 1000 Mbps Ethernet fibre or four 10/100/1000 Mbps copper ports (requires SFP transceivers)
- Up to twelve on-board transcoding Digital Signal Processor (DSP) modules
- Inline QoS measurement processors
|
Enhanced Traffic Control Interface Unit |
- Four 1000 Mbps Ethernet fibre or four 10/100/1000 Mbps copper ports (requires SFP transceivers)
- Integrated high-capacity encryption (IPsec, SRTP, TLS) processors
- Inline QoS measurement
- Integrated hardware-based SIP-TLS and TCP processing
|
Network Interface Unit Management Interfaces - included on all NIU options |
- Two 10/100/1000 Mbps interfaces with RJ-45 for HA node configurations
- One 10/100/1000 Mbps interface with IPsec encryption processor and RJ-45 for management networks
(Optional IPsec encryption of management interface via encryption capable NIU)
- One RS-232 serial console interface with RJ-45 connector (only rear or front interface may be used
at any time)
- One alarm interface with RJ-45 connector
|
|
AC Power |
- Single or dual field-replaceable power supplies
- Dual power supplies: Redundant, load sharing, 300 VA maximum
- Voltage: Autoranging 100 AC to 240 AC wide input with power factor correction
- Frequency: 50/60 Hz
- Current: 3A × 2 rating
- Cable: 2.0m 18 AWG three-wire cable, with three-lead IEC 320 receptacle on the power supply
end and a country-dependent plug on the power source end
|
-48 DC Power |
- Single or dual field-replaceable power supplies
- Dual power supplies: Redundant, load sharing, 300 VA maximum
- Voltage: -48 DC (+/− 10%) nominal in North America (maximum range: -40 DC to -60 DC)
- Current: 7A × 2 rating
- Cable: 18 AWG recommended minimum, with at least three conductors rated for at least 60° C (140° F)
|
-72 DC Power |
- Voltage: -72 DC nominal in Russia
- Cable: 18 AWG recommended minimum, with at least three conductors rated for at least 60° C (140° F)
|
Temperature |
Operating: +0° C to +40° C (32° F to 104 ° F)
Nonoperating: -20° C to 65° C (-4° F to 149° F) |
Relative Humidity |
Operating: 10% to 85% (non-condensing) |
Altitude |
Operating: 3048m (10000 ft) (max) |
Air Flow |
50 CFM front to back |
Heat Dissipation |
Typical: 100W (341 BTU/hr)
Maximum: 200W (682 BTU/hr) |
Power Dissipation |
Typical: 100W
Maximum: 200W |
|
Height |
4.37 cm (1.72 in) |
Width |
43.43 cm (17.10 in) |
Depth |
48.26 cm (19 in) |
Weight (maximum) |
8.62 kg (19 lb), fully configured |
|
Overall |
European Compliance (CE) marking indicating compliance with the
99/5/EC directive which includes the following European Norm (EN)
and IEC standards for safety and electromagnetic compatibility |
Safety |
US: UL 60950-1 Second Edition
Canada: CSA-C22.2 No. 60950-1-07, Second Edition
C22.2 No. 60950-1-03, First Edition
EU: EN 60950-1:2006 |
Electromagnetic Compatibility (EMC) |
US: FCC Part 15 (CFR 47), Class A Limits
Canada: ICES-003 Issue 4, Class A Limits
EU: EN 55022:2006 + A1:2007 Class A Limits
Australia: CISPR 22 and C-Tick
Japan: VCCI Class A Limits |
Immunity |
EU: EN 300 386 v1.4.1 |
NEBS |
GR-63
GR-1089
SR-3580: Level 3 Certified |
US Department of Defense Security |
FIPS 140-2 Compliant
DISA Unified Communication Requirements (UCR) Compliant
Listed: DISA Unified Capabilities Approved Product List (UCAPL) |
|
Front or center mounted in 19" wide racks (up to 28" deep) with options for 23" wide racks. |
Clearance
and Service Access
|
Front |
20 cm (8 in) |
Rear |
10 cm (4 in) |
Leave enough clearance, approximately 20 cm (8 in), in front of the equipment rack
to allow access to the consolde connector, reset button, graphic display buttons,
and physical interface card slots. |
Leave enough clearance, approximately 10 cm (4 in), in the rear of the equipment rack
to allow for sufficient airflow and for ease in cabling and/or servicing the rear panel. |